Project Name

TECOM Investments Warehouse

Ibtikar Fireproofing is a UAE Civil Defense-approved contractor delivering passive fire protection for structural steel. We protect industrial, commercial, and infrastructure assets with certified intumescent coating systems.

TECOM Investments client logo

Project Snapshot

Certified passive fire protection and intumescent coating specifications for structural steelwork.

31,000

Total Surface Area

60 Min

Fire Resistance Rating

Nullifire SC802

Intumescent Basecoat

Carbothane 137HS

Protective Topcoat

100%

UAE Civil Defense Approved

April 2024

Completion Date

Fire Proofing Materiel

Nullifire SC802 | 60-Min Water-Based Intumescent Coating

BS 476 & Certifire CF5420 Certified Passive Fire Protection for Internal Structural Steelwork. Optimized single-coat application for 60-minute cellulosic fire resistance.

SC802 Nullifire
Fire Resistance Rating Up to 60 Minutes (Internal Steel)
Volume Solids 70% ± 3%
Density / Specific Gravity 1.38 ± 0.02 kg/L
Coverage (Theoretical) 979 g/m² @ 0.5 mm DFT
Max Wet Film Thickness (WFT) 1.0 mm/coat spray, 0.6 mm brush
VOC Content ≤ 16 g/L
Application Method Airless Spray or Brush/Roller
Pack Size & Storage 25 kg Drums (Protect from Frost)

Source: Nullifire SC802 Technical Data Sheet (Tremco CPG), tested to BS 476: Parts 20/21. Your catalog page also mentions a "limited 90-minute option" — this data sheet only confirms 60 minutes, so verify the 90-minute claim before publishing.

Substrate Preparation

  • Steel Preparation: Apply only onto a clean, undamaged, dry, primed steel surface free from contaminants.
  • Substrate Restrictions: Only primers listed in the product's ETA (European Technical Assessment) or on Nullifire's website are pre-approved.

Primer Systems

  • Nullifire's recommended primers are listed in the SC802 ETA and on Nullifire's website. Contact Nullifire technical services for compatibility testing on any primer not already listed.

Airless Spray Application Setup

  • Operating Pressure: 2500–3000 psi (175–210 kg/cm²)
  • Tip Size: 17 to 21 thou
  • Fan Angle: 20°–40°
  • Fluid Line: 10 mm (3/8") ID

Drying Schedule (at 20°C)

Dry Time @ 0.2mm WFT 2 Hours
Dry Time @ 0.5mm WFT 3 Hours
Dry Time @ 1.0mm WFT 4 Hours

Times shown are recoat intervals at 20°C and vary with temperature and humidity — confirm with Nullifire for your site conditions.

Third-Party Certifications & Compliance

  • Certifire CF5420 — third-party approval.
  • Tested to BS 476: Part 20/21 for internal structural steelwork.
  • Cellular beam assessment: YB5.

Technical Documents

All four links are placeholders. Note: an SC802 Safety Data Sheet is already hosted on your Saudi site (ibtikar-saudi.com) — happy to link that or your own UAE media-library copy once you confirm which to use.

Fire Proofing Materiel

Carbothane 137HS | High-Build Polyurethane Protective Topcoat

Fast-Drying Two-Component Coating for Direct-to-Metal Application in C1–C3 Environments. Outstanding UV and Gloss Retention for Long-Term Exterior Performance.

Carbothane 137HS coating product logo
Fire Resistance Rating N/A — Protective Topcoat
Recommended Environment C1–C3 (No Primer), C4–C5 (With Primer)
UV / Gloss Performance Outstanding UV & Gloss Retention
VOC Content 328 g/L (Part A, as supplied)
Volume Solids Not published in sources checked
Max Dry Film Thickness (DFT) Not published in sources checked
Application Method Not published in sources checked
Pack Size & Storage Not published in sources checked

Sources: Carboline regional product page (environment, UV/gloss) and the Carbothane 137HS Part A Safety Data Sheet already hosted on your own site (VOC content). Carboline's official TDS PDF is blocked to automated access (robots.txt) — I could not pull volume solids, DFT or pack size from it. If you can download it from your Carboline rep or account, send it over and I'll fill in the rest with real numbers instead of leaving them blank.

Substrate Preparation

  • Corrosivity Category: Suitable for direct-to-metal application in C1–C3 environments without a primer.
  • Higher Corrosivity: For C4–C5 environments, apply over an appropriate Carboline primer system.

Primer Systems

  • Specific primer product names/DFT ranges were not published in the sources I could access — confirm the approved primer system with Carboline for your substrate and corrosivity category.

Application

  • Two-component polyurethane, mixed per Carboline's stated ratio before application (ratio not published in the sources checked).
  • Formulated for fast-drying, high-build application with excellent dry times relative to standard polyurethane topcoats.

Drying Schedule

Specific tack-free, recoat and full-cure times were not published in the sources I could access for this product — Carboline's official data sheet is blocked to automated fetching. Confirm with Carboline or your TDS copy before publishing exact hours.

Third-Party Certifications & Compliance

  • No third-party fire or corrosion certifications were found in the sources checked for this specific product — as a topcoat it is typically used as part of a certified system rather than certified on its own. Confirm with Carboline if a specific approval is required for your project.

Technical Documents

The Part A SDS link above is already live on your own site. The other three are placeholders — point them at your hosted TDS / Part B SDS / certificate once confirmed.

On-Site Project Demo

Fireproofing Spray Application

On-site airless spray application of certified passive fireproofing coatings on structural steel framework.

Proven Track Record

Previous Projects

Explore our portfolio of certified passive fire protection and structural steel coating developments across the UAE and GCC.

TECOM Investments Warehouse fireproofing project by Ibtikar Fire Proofing
AWR Distribution Center DIC fireproofing project by Ibtikar Fire Proofing
Abu Dhabi Future School Phase 10 fireproofing project by Ibtikar Fire Proofing
RSA Cold Chain Phase 2 facility fireproofing project by Ibtikar Fire Proofing